The JD150K385H4 series are designed for class I (class B) protection of three-phase AC power supply against lightning over-voltage destruction
MAIN FEATURE:
Three phases AC power supply: 3+1 circuit, fits for TT and TN system;
Especially selective parameter of apparatus fits even more to defend equipment in poor-quality power net-work;
Temperature control to shut-off technology and built-in over-current protection circuit avoid fire accident entirely;
Low residual voltage, well protect customers equipment;
Red, Green colors LEDs indicate operating state syllabify and straightly;
Remote alert function makes your control easy;
Small size, expedient installation and simple maintenance;
Rarefied craftwork, Can work permanently on bad circumstance.
PARAMETERS
Model
JD120K385H4(J)
JD150K385H4(J)
Nominal voltage Un
Three-phase 220V / 380V
Max Continuous operating voltage Uc
385V
Nominal discharge current In
50kA(8/20µs)
60kA(8/20µs)
Maximum discharge current Imax
120kA(8/20µs)
150kA(8/20µs)
Protection level Up(8/20µs)
L-N mode
U20kA<=1500V
U30KA<=2000V
U20kA<=1500V
U25KA<=2500V
N-PE mode
U20kA<=600V
U30KA<=1000V
U20kA<=600V
U25KA<=1200V
Sensitivity of lightning counter
<=3kA(8/20µs)
Response time
<=25ns
Connecting cable section area
10mm2-35mm2
Dimensions
450mm×330mm×150mm
Working environments
Temperature 40°~+70°, Humidity relative 5~95% (25°) , Altitude<=3km
INSTALLATION
1. The protection box should install close to the general power distribution cabinet (Chart 1)
2. The connection of the SPD
2.1 The protection box connection way, please check attached instruction. .
2.2 There is alarm transit port on the SPD (normally low impedance, failure high impedance. ) . Connection port is on the plate inside the case. If long distance control needed, just plug the alert device in open circuit. .
2.3 Check all the connections, then electrify, All indicators green shows the lightning protection box normal.
NOTICE
Shut down power supply before installation. The connecting cable must be up to standard.
If system operating current of A is more than 100A, B (a air breaker or meltable fuse of 63A) is necessary. (chart 3)
When the LED lights are in green it shows the SPD is normal, if they are red, that means the SPD has fault and need to be replaced immediately.
When remote alarm spring, check protection box carefully, the failure part must be replaced immediately.
No special maintenance was needed. Check the connection state, working state and LED once a period.
Category :
Surge Suppressors
Related Searches :
,
,
,
Country Of Origin :
China
Listing Type :
Sell
Brand Name :
DOWIN
Model Number :
JD150K385H4 (J)
Condition :
New
Warranty :
3 year
Certifications :
ISO9001,CE
Contact :
serena Liu
Address :
4/F-A&B, Technology Building,
Industry 7th Road,shekou
Shenzhen, Guangdong, 518067
China
Telephone :
[86] (0755) 26889911 (ext 8927)
Fax :
[86] (0755) 26889922