Sell Load sharer PER672

Load sharer PER672 You May Also Be Interested In: load sharer load sharing
1) Description----The function of the Load Sharing Module is to proportionally share load between two or more generator sets while the system frequency is held constant. As an accessory to the electronic Governing System, the PER 672 measures the true power current , and throught a parallel cable interconnection, continuously controls the governor system.


2) Performance
Load SharingAdjustable to within +/-2% between sets
Performance. Isochronous and droop paralleling and power control
Reverse Power Monitor. Adjustable from 0.5-20% with a 2 second inverse time constant
Forward Power MonitorONtrip point adjustable from 20-100%
OFFtrip point adjustable from 0-80%
Normally open contacts with a 2 second inverse time constant


3) Power Output

Signal.0 to 7.5 Volts DC representing 0-100% load
All performance specifications are based on 5 amps from the current transformer(CT) Secondaries at full load unity P. F.


4) Power input
AC input signals. . 208 or 416 volt nominal line to line and 5 amp CTs with a minimum 6.25 VA rating. Internal 0.25 ohm burden resistors
Line to line voltagesper table below
HZ LOW RANGE HIGH RANGE
50 140-250 VAC 260-420 VAC
60 170-260 VAC 340-500 VAC
400 170-260 VAC 340-500 VAC


DC Supply. .18-36 VDC(Transient and reverse voltage protected)
DC Power Consumption.70 ma continuous


5) Weight:2.41kg
Supply Capacity
1000PCS
Lead Time from Order to Shipment
1day
Model Number
PER672
Minimum Order Quantity
1pcs
Terms of Payment
T/T
Terms of Sale
CNF
Weight
2.41kg